Influence of mixing valve dynamics and recirculation loop connection to solar tank on large hot water system performances - CEA - Commissariat à l’énergie atomique et aux énergies alternatives Access content directly
Journal Articles Solar Energy Year : 2021

Influence of mixing valve dynamics and recirculation loop connection to solar tank on large hot water system performances

Abstract

A centralized solar domestic hot water system for a multi-family building is analyzed numerically. The solar preheated water in the solar tank is flowing into an auxiliary tank, connected to a gas boiler. At its output, a mixing device is used to ensure hot water at steady temperature before going through the recirculation loop. This reference system is sized as a typical installation under mild climate in France. The load profile is generated statistically with a one-minute time step. Small time scale phenomena have consequences on the global system behavior: recirculation flow rate variations due to pressure drop change is modeled and validated experimentally. This work's goal is to analyze these effects on two sub-parts of the plant: mixing valve and recirculation loop connection to solar storage. In each case, yearly simulations with 6 s time step provide quantitative performance indicators for different sizing and control options. Results show that mixing valve slow response, due to ageing or bad design, leads to a loss of 3.5% energy savings compared to using a fast component. Furthermore, health risks increase as the minimal temperature in the recirculation loop is often under 50 • C, which promotes legionella development due to cold water plug flows generated in the loop by the mixing valve dynamic response. The recirculation loop, linked to a solar tank, leads to performance improvement with 6-15% increase in energy savings following solar oversizing and reduced overheating risks.
Fichier principal
Vignette du fichier
acceptedManuscript_SDHWSystems.pdf (2.29 Mo) Télécharger le fichier
Origin : Files produced by the author(s)

Dates and versions

cea-03167394 , version 1 (12-03-2021)

Licence

Attribution - NonCommercial - NoDerivatives

Identifiers

Cite

Arnaud Becq, David Chèze. Influence of mixing valve dynamics and recirculation loop connection to solar tank on large hot water system performances. Solar Energy, In press, 218, pp.211 - 225. ⟨10.1016/j.solener.2021.02.012⟩. ⟨cea-03167394⟩